iCOR is a non-destructive testing (NDT) device that detects and measures the rate of rebar corrosion in concrete structures.
iCOR’s half-cell potential measurement aligns with ASTM C876. For corrosion rate, there is no universally recognized standard, iCOR uses the well-established Stern-Geary equation (polarization resistance method), which is widely documented in research but not yet codified in a single named standard. For surface resistivity, iCOR uses a modified application of the four-probe Wenner array methodology, the same principle as AASHTO T358, adapted for field use over reinforced concrete.
Surface resistivity and corrosion-rate measurements do not require a rebar connection. Half-cell potential testing does require a connection to a continuous reinforcing bar, but this mode is optional and used alongside the other measurement modes rather than as a standalone requirement.
Yes, iCOR integrates resistivity testing alongside corrosion-rate measurement in a single device.
Yes, standard half-cell potential testing requires an electrical connection to the reinforcing steel.
There is no formally defined maximum distance between the rebar connection point and the probe measurement location for half-cell potential testing. In practice, accuracy can degrade over longer distances due to increasing electrical resistance in the rebar network. The connection point should be kept as close as reasonably possible to the survey area, and continuous rebar connectivity between the connection point and measurement area must be maintained.
By combining resistivity/potential readings at multiple grid points, the software maps variations to highlight likely corrosion zones.
Yes. The surface should be brought to a saturated-surface-dry (SSD) condition: wet the test area thoroughly for ionic conductivity, then let it drain for about 15-20 minutes so it’s damp with no standing water at the electrodes.
iCOR reads reliably with concrete cover of roughly 10-90mm over the reinforcement. Outside that range, measurement reliability drops. Readings are temperature-corrected for standardized conditions.
Yes, mix composition affects the resistivity signature, so interpretation should account for your specific mix.
Yes, rebar diameter and other parameters can be pre-configured to improve interpretation.
iCOR is primarily designed for conventional reinforcing steel; confirm applicability for post-tensioned cables with Giatec’s team.
Yes, iCOR‘s software supports contour mapping of corrosion risk plus both raw data and interpreted results output.
Yes, iCOR‘s reporting output is commonly used to support research documentation and funding proposals.
Consumables, including conductive gel or contact sponges for good electrical contact, are available through Giatec or authorized distributors.
In most cases yes. Check current OS/device compatibility with your rep.
Yes. Calibration is available as a service; turnaround is roughly a few weeks depending on standard and backlog.
Calibration is generally infrequent for the device itself; baseline readings should be re-established if key conditions change.
Institutions can purchase iCOR directly from Giatec in most regions. Some jurisdictions require an open tender if equivalent equipment is locally available, in which case Giatec will connect you with an authorized distributor. Contact Giatec or submit a distributor inquiry to find the right purchasing pathway for your institution.
Yes, Giatec can provide preliminary quotes and documentation to support budgeting before final procurement.
Training sessions covering device operation and data interpretation are available on request.
iCOR combines several of these capabilities into a single device, reducing the need for multiple standalone tools.
Pricing is quoted per device/configuration; standard academic discounts (commonly around 10%) are generally available.
Yes, iCOR is commonly used in forensic and condition-assessment work to identify and map corrosion risk.
Perma is a 4-channel laboratory instrument that measures the rapid chloride permeability of concrete (RCPT). It quantifies the total electrical charge passed through a concrete specimen under 60V DC over 6 hours, which indicates the material’s resistance to chloride ion penetration, a key concrete durability parameter.
Perma is designed to comply with ASTM C1202 (Standard Test Method for Electrical Indication of Concrete’s Ability to Resist Chloride Ion Penetration), which is also equivalent to AASHTO T277.
The ASTM C1202 test itself runs for 6 hours. Specimens must also be vacuum-saturated beforehand: 3 hours of vacuum, 1 hour vacuum with water, then an 18-hour soak, approximately 22 hours of preparation before the test begins.
ASTM C1202 requires a 50mm thick disc cut from a 100mm diameter concrete core or cylinder.
Yes. ASTM C1202 is widely referenced in project specifications for low-permeability concrete. Results are reported in coulombs and classified as: High (>4000 C), Moderate (2000 to 4000 C), Low (1000 to 2000 C), Very Low (100 to 1000 C), and Negligible (<100 C).
Perma operates as both a standalone bench instrument (with live readings displayed on screen) and a software-connected device. For data logging and reporting, it connects via USB to a PC running Giatec’s Data Monitor software, which records current, temperature, and cumulative charge passed in real time.
Perma ships with a device verification kit for routine accuracy checks. Run verification before each test program or whenever results appear inconsistent. If the device fails verification, contact Giatec for service.
Yes, training is available upon request. Contact your Giatec representative to arrange an in-person or virtual session for your lab team.
The only consumables required per ASTM C1202 test are two chemical solutions: a 3.0% sodium chloride (NaCl) solution and a 0.3N sodium hydroxide (NaOH) solution. Both are standard lab reagents available from any chemistry supplier. Test cells and hardware are reusable.
Owning a Perma unit lets you run up to 4 specimens simultaneously in-house, eliminating third-party lab turnaround and shipping time. This is particularly valuable for time-sensitive QC programs and accelerated curing protocols.
Yes. When connected via USB, Giatec’s Data Monitor software logs the complete test record, current readings, specimen temperature, and total charge passed (coulombs), which can be saved and used for QC records, submittals, or regulatory documentation.
Pricing is available upon request. Contact your Giatec sales representative for a quote and ask about institutional and academic pricing.
RCON2 measures bulk electrical resistivity of concrete using AC impedance spectroscopy. It applies an alternating current across the full cross-section of a cylinder via plate electrodes and measures the resulting impedance, giving a bulk resistivity value in kOhm-cm that reflects the concrete’s pore structure and durability.
RCON2 is designed to comply with ASTM C1876-19 (Standard Test Method for Bulk Electrical Resistivity of Hardened Concrete). It also supports testing beyond the standard, including fresh concrete resistivity and a frequency sweep from 1 Hz to 30 kHz for detailed material characterization.
Bulk resistivity (RCON2) uses plate electrodes on both flat ends of a cylinder to measure resistance through the full specimen cross-section. Surface resistivity uses a 4-probe Wenner array on the curved surface. ASTM C1876 governs bulk resistivity; AASHTO T 358 governs surface resistivity. The two methods are related but not directly interchangeable.
RCON2 accepts standard 4×8″ and 6×12″ cylinders and 100mm cubes. For non-standard geometries, a custom geometry factor can be entered. For cores, the length-to-diameter ratio should be at least 1:1 and the minimum specimen dimension must be at least three times the maximum aggregate size.
Per ASTM C1876-19, specimens should be submerged in simulated pore solution (NaOH + KOH + Ca(OH)2) for at least 6 days at 23 +/-2°C before testing. This saturates the pore network and ensures consistent, comparable results.
ASTM C1876-19 requires a conductive fluid for the electrode sponges: Ca(OH)2-saturated water, simulated pore solution, or a manufacturer-supplied fluid. Distilled or deionized water is not recommended as it can affect result accuracy.
Bulk electrical resistivity is temperature dependent, so ASTM C1876-19 requires all specimens to be tested at 23 +/-2°C. RCON2 measures at the specimen’s current temperature and does not apply automatic temperature correction. Contact your Giatec representative to confirm whether the current Data Monitor software version includes a temperature normalization option.
RCON2 ships with a verification kit to validate accuracy across its operating range. Run verification before each test program. If any channel fails, return the device to Giatec for service.
RCON2 is designed as a bench instrument for lab use, the specimen setup under plate electrodes is not practical in the field. For field resistivity testing, the 4-probe Wenner array (Surf) is the portable alternative. For in-situ concrete monitoring, SmartRock Pro is better suited.
The primary consumable for RCON2 is the conductive gel or solution used with the electrode sponges (the sponges themselves are reusable with proper care). For fresh concrete testing, the metal probe rods inserted directly into the mix are also consumables.
RCON2 bulk resistivity results in kOhm-cm correlate to chloride penetrability classifications: High (<4 kOhm-cm), Moderate (4 to 8 kOhm-cm), Low (8 to 16 kOhm-cm), Very Low (16 to 190 kOhm-cm), and Negligible (>190 kOhm-cm). These correlations are documented in the RCON2 user manual and are referenced in AASHTO T358 and AASHTO PP84.
Yes. RCON2 includes a fresh concrete sample holder with steel probe rods that act as electrodes, allowing resistivity monitoring from early age. This is useful for tracking hydration and evaluating mix design performance in real time.
SURF is a laboratory instrument that measures surface electrical resistivity of hardened concrete cylinders and cores using a 4-electrode Wenner array. Its sealed sample holder positions four electrode sets simultaneously at 90° intervals, taking all required measurements at once without manual rotation.
RCON places plate electrodes on both flat ends of a cylinder and measures resistance through the full cross-section (bulk resistivity). SURF uses a 4-pin Wenner probe on the curved longitudinal surface and measures resistivity near the surface layer. Both assess chloride penetration resistance, but through different measurement approaches and reference standards, so results are not directly comparable.
SURF complies with AASHTO T 358 (Standard Method of Test for Surface Resistivity Indication of Concrete’s Ability to Resist Chloride Ion Penetration). There is no finalized ASTM standard for surface resistivity at this time.
SURF’s enclosed sample holder is designed for standard 4×8″ (100mm x 200mm) cylinders. The optional handheld probe extends compatibility to 6×12″ cylinders, cores drilled from existing structures, and other non-standard geometries.
Yes, surface moisture significantly affects SURF readings. Samples must be kept at 100% relative humidity from demolding through testing, with the surface saturated at the moment of measurement. Drier surfaces produce artificially high resistivity readings. SURF’s enclosed sample holder is designed to retain moisture and reduce evaporation between readings.
Yes. SURF output maps to AASHTO T 358 chloride penetrability categories (High, Moderate, Low, Very Low, Negligible), which are widely accepted in durability-related specifications and DOT requirements.
SURF ships with two verification dongles, one for the low range (below 100 kOhm-cm) and one for the high range (100 to 1000 kOhm-cm). Run both across all four measurement channels before each test program. If any channel fails, contact Giatec for service.
SURF requires three consumables: conductive gel (for electrode contact in the sample holder), conductive pads (16 are included; reusable across many tests), and sponges (used with the optional handheld probe, wetted before each test). Replacement consumables are available from Giatec.
Yes. Mix composition directly affects concrete resistivity, water-to-cement ratio, cement type, and supplementary cementitious materials (SCMs) such as fly ash or slag all influence SURF readings. This is expected behavior: SURF is measuring a real material property that varies with mix design.
SURF comes with Data Monitor software that guides users through setup and data entry, and the User Manual covers sample preparation, the full test procedure, and troubleshooting. For hands-on training, contact your Giatec representative to arrange a session.
Pricing depends on configuration and region. Contact Giatec or your authorized distributor for a quote. Academic and volume pricing options may be available.
SmartRock® Long Range monitors every floor of your vertical build. Proven on a 64-story Miami tower. Get a quote today!
SmartRock® shows the exact hour your concrete is ready, so heaters shut off on data, not guesswork.